p. 2

Thermal Management Products & Accessories from SAN successfully used worldwide Problem: Condensation forms due to fluctuating temperature, even in sealed enclosures. In combination with dust and aggressive gases condensation causes corrosion which results in stray currents and arcing. Too high a temperature, or for that fact too low a temperature, can also lead to serious component failure. The safety risk is enormous and the cost of operational delays as a consequence is incalculable. Solution: Only constant optimum climatic conditions allow components to function properly. The right climate can be attained by a temperature and moisture control system. When temperatures are too low or when temperature differences (e.g. night / day) are large, heating is required. It may also be necessary to keep components cool by controlled ventilation. Applications: Whether for telecommunications or traffic systems, power stations or outdoor plants, ATMs or parking control system, where electronics have to be protected against humidity, heat or cold, SAN’s comprehensive product range offers effective economical solutions. Our Products: Conventional and PTC semi-conductor control panel heaters and fan-assisted heaters ranging from 5W to 1200W, as well as tropicalised and EX variations. Temperature and humidity controls ranging from 0°C to 60°C (30° to 140°F) and 35% to 100% RH. A new filter fan series in EMC and standard versions with excellent performance and shielding characteristics. Panel lighting and accessories. About us: We have been developing and producing innovative products for thermal management for more than twenty years. Our products are renowned for their reliability and long life, simplicity of use and high quality. Used and proven worldwide even under extreme conditions. for control panels and enclosures for traffic control and monitoring systems in the transport industry for high voltage swichtgear in outdoor and indoor substations system protction in the automotive industry in transmitter stations of cellular phone networks for motor control centres and control cabinets 2

[close]

p. 3

Contents: Heating: Small semiconductor heater RCE 016 Series................................................... 4 Small semiconductor Heater RC 016 Series..................................................... 5 Small semiconductor Heater HGK 047 Series.................................................. 6 Small semiconductor Heater CSK 060 Series.................................................. 7 Finned extruded Heater SAN-FXE.................................................................... 8 Semiconductor Heater HG 140 Series.............................................................. 9 Compact Fan Heater HGL 046 Series............................................................... 10 Hazardous area Heaer CREx 020 Series........................................................... 11 Electrical Direct Heater SAN-LP........................................................................ 12 Electrical Space Heater SAN-LP AF Ex Heater................................................. 13 Electrical Smart Heater SAN-SMLP.................................................................. 14 Semiconductor Heater CS 060 Series.............................................................. 15 Semiconductor Heater CSF 060 Series............................................................ 16 Small semiconductor Fan Heater CS 028 Series.............................................. 17 Compact semiconductor Fan Heater CSL 028 Series...................................... 18 Electrical Smart Heater SAN-GSMLP............................................................... 19 Explosion proof Heater SP................................................................................ 20 Electrical Smart Heater..................................................................................... 21 Electrical Smart-Space Ex Heater SM-*A......................................................... 22 Electrical Direct Ex Heater CS-*S...................................................................... 23 Electrical Direct Ex Heater CT-*A...................................................................... 24 Anti Condensation and Space Heater SAN-HEF.............................................. 25 Space-saving Fan Heater HV 031 / HVL 031 Series......................................... 26 Semiconductor Fan Heater CR 027.................................................................. 27 Fan Heater with integrated thermostat or hygrostat CR 030............................ 28 Fan Heater with integrated thermostat or hygrostat CR 130............................ 29 Fan Heater with/without integrated thermostat CS 030................................... 30 Fan Heater with/without integrated thermostat CS 130................................... 31 Low maintenance Filter Fan FF 018 Series (21m3/to 102m3/h)......................... Low maintenance Filter Fan FF 018 Series (200m3/h)....................................... High-performance Filter Fan FF 018 Series (300m3/h)...................................... High-performance Filter Fan FF 018 Series (550m3/h)...................................... Outdoor Filter Fan FF 018 Series...................................................................... Low noise Roof Filter Fan RFF 018 Series........................................................ High-performance 19” Fan Tray LE 019 Series................................................. Ventilating: Regulating and monitoring: 32-33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 Electronic Relay SM 010 (DC 24V + DC 48V).................................................... Small, compact Thermostat KTO 011 / KTS 011.............................................. Fix Thermostat FTO 011 / FTS 011................................................................... Dual Thermostat ZR 011................................................................................... Dual Thermostat FTD 011................................................................................. Mechanical Thermostat FZK 011...................................................................... Electronic Thermostat ET 011 (DC 24V)............................................................ Ex FixTherm96 Thermostat............................................................................... FixTherm96 Thermostat.................................................................................... Mechanical Hygrostat MFR 012........................................................................ Electronic Hygrostat EFR 012........................................................................... Electronic Hygrottherm ETF 012....................................................................... Hazardous area Thermostat REx 011 Series.................................................... Lighting: Slimline Lamp with on/off switch SL 025 Series............................................... Slimline Lamp with movement sensor SL 025 Series....................................... Dual Lamp with on/off switch DL 026 Series.................................................... Dual Lamp with movement sensor DL 026 Series............................................ Hand Lamp with lamp holder DL 026 Series.................................................... Compact Lamp KL 025 Series.......................................................................... Accessories: Electrical Sockes SD 035 Series .................................................................... Pressure compensation Device DA 084............................................................ Pressure compensation Device DA 284............................................................ Pressure compensation Device DA 284 (stainless steel).................................. Self-adhesive appliance holder SANOFIX......................................................... Calculation of temperature control in encloseures............................................ Indication of measurements in m.m. Errors and omissions excepted. Specifications are subject to change without notice. Suitability of the products for their intended use and any associated risks must be determined by the end customer/buyer in their final application. 3

[close]

p. 4

Heater - RCE 016 Series • • • • • Temperature limiting Wide voltage range Dynamic heating up Energy saving Compact 5W, 9W Small semiconductor Small heaters designed to prevent condensation and to ensure a minimum operating temperature in small enclosures. Technical Data: Operating voltage Heating element Heater body Mounting Fitting position Dimensions Op./storage temperature Prot. type / Prot. class Approvals Accessories Note 12-240V AC/DC* (min. 110V, max. 265V) PTC resistor, temperature limiting Aluminum See Accessories Variable Length 45mm, Ø10mm -45 to +70ºC IP32 / II (double insulated) VDE + UL File No. E150057 Mounting clips (see illlustration) Other voltages on request *) Op. with voltages below AC/DC 140V reduces heating performance by approx. 10%. Example of connection Thermostat KTO 011 (contact breaker, normally closed) Heater RCE 016 Connection 2xAWG 22 sheathed cable (silicone) L N Mounting clips Art. No. (1 packing unit = 2 pieces) Art. No. 82240 82241 82242 82243 120-240 12-36 120-240 12-36 Voltage Heating capacity* 5W 5W 9W 10W Inrush current max. 2.0A Surface temp. (approx.) 165˚C 2xAWG 22 sheathed cable (silicone) 2xAWG 22 sheathed cable (silicone) Connection Weight (approx.) 20g 2.5A 175˚C 20g * At 20ºC (68˚F) ambient temperature. 4

[close]

p. 5

Heater - RC 016 Series • • • • • Temperature limiting Wide voltage range Dynamic heating up Energy saving Compact 8W, 10W, 13W Small semiconductor These small heaters are designed to prevent condensation and to ensure a minimum operating temperature in small enclosures. Technical Data: Operating voltage Heating element Heater body Mounting Fitting position Op./storage temperature Prot. type / Prot. class Approvals Note 120-24V AC/DC* -(min. 110V, max. 265V) PTC resistor, temperature limiting Aluminium, anodised Screw fixing Variable -45 to +70ºC (-40 to +158˚F) IP32 / II (double insulated) VDE + UL File No. E150057 Other voltages on request Art. No. : Connection 2xAWG 18 stranded wire *Op. with voltages below 140V AC/DC reduces heating performance by approx. 10%. Example of connection Thermostat KTO 011 (contact breaker, normally closed) Heater RC 016 Art. No. : Connection 2xAWG 22 sheathed cable (silicone) Art. No. : Connection 2xAWG 22 sheathed cable (silicone) L N Art. No. 82244 82246 82248 82243 82247 82249 Heating capacity* 8W 10W 13W 8W 10W 13W Inrush current max. 2.0A 2.5A 3.0A 3.7A 5.7A 10.0A Surface temp. (approx.) 150˚C 155˚C 170˚C 134˚C 132˚C 148˚C 2xAWG 18 stranded wire 2xAWG 22 sheathed cable (silicone) 2xAWG 22 sheathed cable (silicone) 2xAWG 18 stranded wire 2xAWG 22 sheathed cable (silicone) 2xAWG 22 sheathed cable (silicone) Connection Weight (approx.) 20g 28g 34g 20g 28g 34g * At 20ºC (68˚F) ambient temperature. 5

[close]

p. 6

10W to 30W Heater - HGK 047 Series • • • • • Dynamic heating up Energy saving Wide voltage range Temperature limiting Clip fixing Small semiconductor The heaters are used in enclosures where condensation is to be prevented or the temperature may not fall below a minimum value. In this way corrosion is avoided and an even temperature is ensured. Technical Data: Heating element Heater body Mounting Fitting position Op. / Storage temp. Prot. type / Prot. class Accessories PTC resistor, temperature limiting Extruded aluminium profile, anodised Clip for 35mm DIN rail, EN 60715 Vertical -45 to +70ºC IP54 / I (earthed) Screw fixing 50 25 Clip for 35mm DIN rail Example of connection Thermostat KTO 011 (contact breaker, normally closed) Heater HGK 047 L N Art. No. 83250 Operating voltage 120-240V AC/DC2) 120-240V AC/DC2) 120-240V AC/DC2) 110-120V AC/DC 110-120V AC/DC 110-120V AC/DC Heating capacity1) 10W 20W 30W 10W 20W 30W Inrush current max. 1.0A 2.5A 3.0A 1.0A 1.5A 1.5A Length (L) 50mm 60mm 70mm 50mm 70mm 100mm Weight (approx.) 0.1kg 0.2kg 0.2kg 0.1kg 0.2kg 0.2kg 300 12 L Connection 3 x 0.5mm2 x 300mm sheathed cable (silicone) 3 x 0.5mm2 x 300mm sheathed cable (silicone) 3 x 0.5mm2 x 300mm sheathed cable (silicone) 3 x AWG 20 x 300mm sheathed cable 3 x AWG 20 x 300mm sheathed cable 3 x AWG 20 x 300mm sheathed cable Approval VDE VDE VDE UL File No. E150057 UL File No. E150057 UL File No. E150057 83253 83252 83251 83254 83255 1) at 20°C ambient temperature; 2) (min. 110V, max 265V) Operating with voltages below 140V AC/DC reduces heating performance by approx. 10%. 6

[close]

p. 7

Heater - CSK 060 Series • • • • • • Low surface temperature Double insulated (plastic housing) Wide voltage range Temperature limiting Dynamic heating up Clip fixing 10W, 20W Touch-Safe Small Semiconductor The heaters are used in enclosures where condensation is to be prevented or the temperature may not fall below a minimum value. In this way corrosion is avoided and an even temperature is ensured. The heaters are designed for permanent operation. Technical Data: Operating voltage Heating element Surface temperature Connection Casing Dimensions Mounting Fitting position Op./storage temp. Prot. type / Prot. class Approvals Note 120-24V AC/DC* -(min. 110V, max. 265V) PTC resistor, temperature limiting <85ºC (according to VDE 0100) except upper protective grille 2-pole terminal 2.5mm2, torque 0.8Nm max. Plastic according to UL94 V-0, black 98 x 38 x 75mm Clip for 35mm DIN rail, EN 60715 Vertical -45ºC to +70ºC IP20 / II (couble insulated) VDE + UL File No. E150057 (according to UL499 in combination with UL508A) Other voltages on request *Op. with voltages below 140V AC/DC reduces heating performance by approx. 10%. Example of connection Thermostat FTO 011 (contact breaker, normally closed) Heater CSK 060 Art. No. Heating capacity* 10W 20W Inrush current max. 1.0A 2.5A Weight (approx.) 0.2kg 0.3kg * At 20ºC (68˚F) ambient temperature. 7

[close]

p. 8

Finned Extruded Enclosure Heater Type SAN-FXE The FXE range of heaters is designed specifically for frost protection, anti-condensation and temperature control within Zone 1 and Zone 2 Hazardous Areas. The FXE delivers a constant power output and comes complete with mounting bracket and a 1.5 metre flying lead. Features • Certified to meet the requirements of the ATEX Directive 94/9/EC, Gost and IECEx. • Compact design, requires minimal space. • Optional over-temperature protection. • Black anodized convective surface. • Standard product available with short delivery times. • Suitable for ambient temperatures -50°C up to +80°C. Typical Applications: Control / monitoring panels Instrumentation cabinets Condensation prevention Temperature fluctuations Frost protection Motor enclosures Certification IECEx & ATEX certified Ex II 2 G/D, Ex d IIC (Gas) T3-T4 Gb, Ex t IIIC (Dust) T200-T135°C Db, EN/IEC60079-0 & EN/ IEC60079-1 & EN/IEC 60079-31 Extrusion Finned Aluminium, Anodized Matt Black Mounting: Vertically Mounted by Bracket or Rail Voltage: Up to 254VAC Rating: Available in 30, 50, 75 & 100 Watts Controls If required, heaters can be supplied with a range of remote mounted thermostats. Element: 18mm dia 321 St/Steel cartridge element with 1.5m silicone flex cable. Weather protection: IP6X 8

[close]

p. 9

15W to 150W Heater - HG 140 Series • • • • • • • Pressure clamp connectors Dynamic heating up Wide voltage range Temperature limiting Energy saving Clip fixing Quick installation Semiconductor These heaters are used in enclosures where damage from condensation must be prevented, or where the temperature may not fall below a minimum value. The aluminium profile heater body design has a chimney effect and distributes the heat evenly. The pressure clamp connectors save time and simplify installation. Technical Data: Operating voltage Heating element Heater body Connection Connection casing Mounting Fitting position Op./storage temperature Prot. type / Prot. class Approvals Accessories 120-240V AC/DC* (min. 110V, max. 265V) PTC resistor, temperature limiting Extruded aluminium profile, anodised 3 pressure clamps for stranded wire 0.5-1.5mm² (with wire end ferrule) and rigid wire 0.5-2.5mm2 Plastic according to UL94 V-0, black Clip for 35mm DIN rail, EN 60715 Vertical -45 to +70ºC IP20 / I (earthed) VDE + UL file E150057 Screw fixing *Op. with voltages below 140V AC/DC reduces heating performance by approx. 10%. Art. No. 83190 83191 83192 83193 83194 83195 *At 20ºC (68˚F) ambient temperature. 83196 Heating capacity* 15W 30W 45W 60W 75W 100W 150W Inrush current max. 1.5A 3.0A 3.5A 2.5A 4.0A 4.5A 9.0A Length (L) 65mm 65mm 65mm 140mm 140mm 140mm 220mm Weight (approx.) 0.3kg 0.3kg 0.3kg 0.4kg 0.5kg 0.5kg 0.7kg 9

[close]

p. 10

Fan Heater - HGL 046 Series • • • • • Compact design Temperature safety cut-out Clip fixing Long service life Maintenance free Compact This compact fan heater prevents the formation of condensation. The integrated axial fan provides forced air circulation and so guarantees an even temperature in enclosures. A built-in temperature safety cut-out switches the heater off, in the event of fan failure. Technical Data: Operating voltage AC 220-240V, 50-60Hz AC 110-120V, 50-60Hz Resistance heater To protect against overheating in case of fan failure. Extruded aluminium profile, anodised Max 75°C (400W) Ball bearing service life 50 000h at 25°C (77°F) airflow 35m³/h, free flow 3-pole clamp for 2.5mm² Clip for 35mm DIN rail, EN 50022 Preferably vertical -40 to +70ºC (-40 to +158˚F) IP20/I (earthed) VDE, UL file E150057 Other voltages on request (e.g. AC/DC 48V) Heating element Temp. safety cut-out Heater body Surface temperature Axial fan Connection Mounting Fitting position Op./storage temperature Prot. type / Prot. class Approvals Art. No. 83256 83257 83257-1 Approval VDE VDE UL UL UL UL Operating voltage AC 230V, 50-60Hz AC 230V, 50-60Hz AC 115V, 50-60Hz AC 115V, 50-60Hz AC 230V, 50-60Hz AC 230V, 50-60Hz Heating capacity* 250W 400W 250W 400W 250W 400W Length (L) 170mm 252mm 170mm 252mm 170mm 252mm Weight (approx.) 1.0kg 1.3kg 1.0kg 1.3kg 1.0kg 1.3kg *At 20ºC (68˚F) ambient temperature. 10

[close]

p. 11

Heater - CREx 020 Series • • • • Large convection surface Clip fixing Ready for use Maintenance free 50W, 100W Hazardous area Compact convection heater for use in areas with explosion hazard for prevention of formation of condensation, temperature fluctuations and for protection against frost in transmitter housings, switch cabinets and measuring equipment. Technical Data: Explosion protection acc. to EN Conformity certificate Heating element Heater body Connection Connection PE Mounting Fitting position Operating/storage temperature Protection type /Protection class LCIE (Laboratoire Central des Industries Electriques) 01 ATEX 6073/03, LCIE No 06 ATEX Q8011, IECEx LCI 07, 0020 High performance cartridge Aluminium profile, black anodised Si HF-JZ 3 x 0.75mm2 cable, length 1m 4mm2 Clip for 35mm DIN rail, EN 60715 Vertical -20 to +40ºC / -45 to 70ºC IP65 / I (earthed) Clip can alternatively be fixed on long side Hazardous area Thermostat REx 011 see page 40 Art. No. 83197 83198 Operating voltage 230-240VAC 230-240VAC Heating capacity* 50W 100W 50W 100W d IIC T5 - Ex tD A21 IP6X T100˚C d IIC T4 - Ex tD A21 IP6X T135˚C d IIC T5 - Ex tD A21 IP6X T100˚C d IIC T4 - Ex tD A21 IP6X T135˚C Ex protection type Surface temperature 100˚C 135˚C 100˚C 135˚C Length (L) 150mm 180mm 150mm 180mm Weight (approx.) 1.3kg 1.5kg 1.3kg 1.5kg 110-120VAC 110-120VAC 11

[close]

p. 12

Electrical Direct Heater SAN-LP Heater Direct-heaters for Hazardous locations, designed for direct mounting onto e.g. manifolds etc. • Freeze protection • Anti-condensation • Temperature maintenance Features and Advantages • • • • • • Certified to meet the requirements of the ATEX Directive 94/9/EC, Gost and IECEx. Self-limiting heating elements Small dimensions No moving parts, no maintenance required therefore long lifetime Suitable for T4 and T3 classifications Can be used for 110 / 240 VAC/DC Description All Cameo Heaters are designed around self-limiting heating elements. These self-limiting semi-conductor elements are saving power consumption. Our Cameo Direct-heaters are designed to heat the installed equipment. If properly selected for freeze protection, no thermostat will be needed. Optional body #5 : 4 holes diam. 5,2 mm. available in Aluminium and SS range For easy mounting, at no extra charge Alternative 316 Stainless Steel heaters can be delivered for the 100-10 Watt range. Also possible is an aluminium body with four holes drilled through (body #5), for easy mounting. Please see below for further technical data. Range LP-1A LP-2A LP-3A LP-4A T3 T4 T4 T4 ca. 115 °C Surface temperature ca. 105 °C Surface temperature ca. 90 °C Surface temperature ca. 70 °C Surface temperature 100-10 Watt 100-10 Watt 100-10 Watt 100-10 Watt High Power model: LP0AHP T3 ca. 130 °C Surface temperature 200-20 Watt * these temperatures are measured at 20 °C ambient temperature. 12

[close]

p. 13

SAN-LP AF Ex Heater Space-heaters for Hazardous locations, designed for : • Freeze protection • Anti-condensation • Temperature maintenance Electrical Space Heater Technical Data: Power consumption Electrical cable Material cable Standard length Other lengths Overall dimensions Material EX protection class Certification Protection degree Voltage Ambient temp. range 100-10 Watt 3x1 sqmm braided silicone, optional: non-braided cable approx. 1 mtr. Other lengths optional To be specified 164x100x60mm (LxWxH) black anodized aluminium II 2G Ex d IIC T4 or T3: II 2D Ex tD A21 IP66 T 135°C or T200°C KEMA 01ATEX2124X and IECEx DEK 11.0017 IP66 110/240 -60°C...+90°C Features and Advantages • • • • • Self-limiting heating elements Small dimensions No moving parts, no maintenance required therefore long lifetime Suitable for T4 and T3 classifications Can be used for 110 / 240 VAC/DC Range LP-1AF LP-2AF LP-3AF LP-4AF T3 T4 T4 T4 ca. 115 °C Surface temperature ca. 105 °C Surface temperature ca. 90 °C Surface temperature ca. 70 °C Surface temperature 100-10 Watt 100-10 Watt 100-10 Watt 100-10 Watt * these temperatures are measured at 20 °C ambient temperature. Description All Cameo Heaters are designed around self-limiting heating elements. These semi-conductor elements are saving power consumption. Our Cameo Space-heaters heat the air inside an enclosure and indirectly the installed equipment. If properly selected for freeze protection, no thermostat will be needed. In other situations, if the equipment, e.g. analyzers, it is normal practice to use our Space-Heters in combination with our Fix-Therm96 thermostats (range from 10°C up to 135°C) Do not cover the fins to guarantee free convection. 13

[close]

p. 14

Electrical Smart Heater for Space Heating SAN-SMLP Ex Heater Space-heaters for Hazardous locations, this compact model is designed for • Anticondensation • Freeze protection • Temperature maintenance • Small spaces Features and Advantages • Certified to meet the requirements of the ATEX Directive 94/9/EC, Gost and IECEx. • Self-limiting heating elements • Small dimensions • No moving parts, no maintenance required therefore long lifetime • Suitable for T4 and T3 classifications • Can be used for 110 / 240 VAC/DC Description All SMART Space-heaters are designed around self-limiting heating elements. These semi-conductor elements are saving power consumption. Our SMART Space-heaters are designed to heat the air inside an enclosure and indirectly the installed equipment. If properly selected for freeze protection, no thermostat will be needed. In other situations, if the equipment may not exceed a maximum temperature value, you can add our Fix-Therm96 thermostat as a maximum temperature protection, in the system. When required in other applications, e.g. analyzers, it is normal practice to use our SMART Space-heaters in combination with our FixTherm96 thermostats (range from 10°C up to 135°C). Do not cover the fins to guarantee free convection.. Range SMLP-1A SMLP-2A SMLP-3A SMLP-4A T3 ca. 115°C Surface temperature T4 ca. 105°C Surface temperature T4 ca. 90°C Surface temperature T4 ca. 70°C Surface temperature 100-10 Watt 100-10 Watt 100-10 Watt 100-10 Watt High power model: SMLP0AHP T3 ca. 130°C Surface temperature 200-20 Watt * these temperatures are measured at 20 °C ambient temperature. 14

[close]

p. 15

Heater - CS 060 Series • • • • • Low surface temperature Quick mounting due to clip fixing Double insulated (plastic) Wide voltage range Small size 50W to 150W Touch-Safe Semiconductor Touch-safe heater for the use in enclosures with electrical/electronical components. The design of the heater supports the natural convection which results in a high air-current of warm air. The surface temperatures on the accessible side surfaces of the housing are kept down as a result of the heater design. Our complete range of thermostats and hygrostats can directly be connected to the heater CS 060. This heater is also available in a version with plug-in thermostat requiring no additional wiring (C*SF 060). Both versions are designed for permanent operation. Technical Data: Operating voltage Heating element Surface temperature Connection Casing Mounting Fitting position Op./storage temperature Prot. type / Prot. class Approvals Note 120-240V AC/DC* (min. 110V, max. 265V) PTC resistor, temperature limiting <80ºC, except upper protective grille 4-pole terminal 2,5mm2, torque 0.8Nm max. Plastic according to UL94 V-0, black Clip for 35mm DIN rail, EN 60715 Vertical -45 to +70ºC IP20 / II (double insulated) VDE + UL file E150057 (according to UL499 in combination with UL508A) Other voltages on request *Op. with voltages below 140V AC/DC reduces heating performance by approx. 10%. Heater CS 060 Heater CS 060 Thermostat FTO 011 Leistungs-Umgebungstemperatur-Diagramm Heating capacity / Ambient temperature diagram CS 060 CS 160 Heating capacity (W) Heizleistung (W) 200 178 160 AC 147 132 150 122 110 Heater CS 060 119 100 66 61 102 93 85 Art. Nr. 16000.0-00 Art. Nr. 16010.0-00 Art. Nr. 16020.0-00 55 50 44 Thermostat FTO 011 50 0 -40 -20 0 Umgebungstemperatur Temperature (ºC) (°C) 20 40 AC Examples of connection Art. No. Heating capacity1) 50W 100W 150W Inrush current max. 2.5A 8A 4.5A Air outlet temp.2) +86ºC +120ºC +145ºC 110 x 60 x 90mm 110 x 60 x 90mm 150 x 60 x 90mm Dimensions Weight (approx.) 0.3kg 0.3kg 0.5kg 1) Ambient temperature - see Heating capacity / Ambient temperature diagram; 2)measured 50mm above protective grille. 15